Din Rail Power Supplies |
OUTPUT | |
Model | DR-75-15 | DR-75-24 | DR-75-48 |
DC Voltage | 15V | 24V | 48V |
Rated Current | 5A | 3.12A | 1.56A |
Current Range | 0-5A | 0-3.12A | 0-1.56A |
Rated Power | 75W | 75W | 75W |
Ripple & Noise | 150mVp-p | 200mVp-p | 400mVp-p |
Voltage Adj. Range | 13.5-16.5V | 24-28V | 48-53V |
Voltage Tolerance | ±2% | ±1% | ±1% |
Line regulation | ±0.5% | ±0.5% | ±0.5% |
Load regulation | ±1% | ±1% | ±1% |
Setup, Rise Time | 500ms,70ms/230VAC 500ms,70ms/115VAC at full load |
Hold Up Time | 36ms/230VAC 32ms/115VAC at full load |
INPUT | |
Voltage Range | 88~132VAC/176~264VAC selected by switch 47~63Hz; 248~370VDC |
AC Current | 2.6A/115VAC 1.6A/230VAC |
Efficiency | 80% | 84% | 85% |
Inrush Current | Cold start 20A/115V 40A/230V |
Leakage Current | <3.5mA/240VAC |
Over Load | 105%~150% rated output power |
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
Over Voltage | 15-16.5V | 29-33V | 58-65V |
Protection type: Shut down o/p voltage, re-power on to recover |
Over Temp. | 85℃±5℃(TSW1) | 90℃±5℃(TSW1) | 90℃±5℃(TSW1) |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down |
Working Temp., Humidity | -20℃~+60℃; 20%~90% RH non-condensing |
Storage Temp., Humidity | -40℃~+85℃; 10%~95%RH |
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC |
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/25℃/70%RH |
Safety Standard | Design refer to UL508,UL60950-1,TUV EN60950-1 |
EMC Standard | Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2), heavy industry level, criteria A |
Dimension | 55.5*125.2*100mm(L*W*H) |
Weight | 0.6Kg |
Packing | 20pcs/carton/13kg |